Products

High Precision Thermocouple Transmitters

High Precision Thermocouple Slimline DIN Rail Transmitter

Technical Features – Input
Thermocouple Types : J, K, R, S, T, B, E & N (as per EN60584.1)
Measurement Range : Settable via dip switch (see input & range table)
Minimum Span : 100°C
Impedance : 10MΩ
Test Current : <50 nA
CMRR(1) : >135 dB (refers to power supply side)
DMRR(1)(2) : >40 dB

Technical Features – Output/Power Supply
Operating Voltage : 19.2 - 30V DC
Consumption : Max. 24mA at 24V DC
Current output : 4~20mA, 0-20mA, 20~4mA or
20~0mA. Max. Load resistance 500Ω
Voltage output : 0-5V DC, 1-5V DC & 0-10V DC. Min.
load resistance 2kΩ
Maximun Voltage : Approx. 12.5V
Maximum Current : Approx. 25mA
Resolution : 1mV for voltage output, 2μA for current
Error: mA & 0-5V DC outputs: 350ppm of end of scale
0-10V DC output: 200ppm of end of scale

Standards
EN61000-6-4/2002-10 (electromagnetic emission, industrial surroundings)
EN61000-6-2/2006-10 (electromagnetic immunity, industrial surroundings)
EN61010-1 (safety)
Other Features
ADC : 14 bits
Class/Base Precision : 0.1%
Thermal Drift : 120ppm/K
Response Time (10-90%) : <25ms (without filter)
<55ms (with repeat filter 50Hz)
Cold Junction Error : 1.5°C Max.
Protection Index : IP20
Sensor Fault Detection : Yes
Box : PBT (black color)
Dimensions/Weight : 6.2 x 93.1 x 102.5mm / 46g
Mounting : Standard 35mm DIN rail
Operating Conditions : Temperature -20 / +65 °C
Humidity 10 - 90% at 40°C
(non-condensing)
Altitude: up to 2000 m.a.s.l
Storage Temperature : -40 - +85 °C
Connections : Spring terminals
Conductor Section : 0,2..2,5 mm²
Wire stripping : 8 mm
Isolation Voltage : 1.5 kV (50 Hz for 1 Min.)
Input and Range Table

 
Input
Range °C
Mean Error
Min Span °C
Resolution °C
Standard
Thermocouple
J
-210... 1200
0.025% + 0.29°C
100
0.12
IEC 60584
K
-200... 1372
0.025% + 0.4°C
100
0.17
IEC 60584
R
-50... 1768
0.025% + 1.19°C
100
0.59
IEC 60584
S
-50... 1768
0.025% + 1.34°C
100
0.66
IEC 60584
T
-200... 400
0.025% + 0.31°C
100
0.13
IEC 60584
B
0... 1820
0.025% + 1.87°C
100
0.90
IEC 60584
E
-200... 1000
0.025% + 0.2°C
100
0.92
IEC 60584
N
-200... 1300
0.025% + 0.42°C
100
0.19
IEC 60584
Table of Accuracy (The sum of A+B or C, whichever is greater)

Nominal Value
Over-range
+/- 2.5%
Over-range
+/- 5%
20mA
20.5mA
21mA
4mA
3.5mA
3mA
0mA
0mA
0mA
10V DC 10.25V DC 10.5V DC
5V DC 5.125V DC 5.25V DC
1V DC 0.875V DC 0.75V DC
0V DC 0V DC 0V DC

Temperature Transmitter Enquiry Form

1. Model

2. Quantity Required

3. Sensor Input

4. Range Details

Range Lower


Range Upper


or Supply unranged?  

Supply TX-PROG
Configuration Software Kit?  

Contact Details

Company Name


Your Name


Email


Telephone


Additional Information

If your enquiry is for more than one type of transmitter, please email us with your requirements or use the box below



Send Enquiry  

BACK TO TOP
Products

Contact Us

About TC

FREE Guide

Privacy Policy

Terms and Conditions

Sitemap
FREE Wallchart Guide

Join over 500,000 engineers and buyers who have already received our FREE 74 page A3 Guide to Thermocouple and Resistance Thermometry

Company Name
  Address 1
Your Name
  Address 2
Title / Dept.
  State
Email
  ZIP Code
Telephone
  Country
Company Name
Your Name
Title / Dept.
Address 1
Address 2
State
ZIP Code
Country
Email
Telephone

We will only ever use the information you provide to occasionally contact you regarding our products and we will never disclose your details to a third party. Our privacy policy can be viewed here



I agree to the terms and conditions listed in the Privacy Policy

View our ISO 90001/2008 Certficate



© 2006- TC Measurement and Control Inc., PO Box 685, Hillside, IL 60162, United States
Tel.: 877 249 1777, Fax: 708 449 0777, Email: info@tc-inc.com