Low Cost DIN Rail Thermocouple and RTD Transmitters
Low Cost Thermocouple and RTD Transmitter - DIN Rail Mounting
Related Products
Mineral Insulated Thermocoupleswith pot seal Mineral Insulated
Resistance Thermometers
with pot seal
Technical Features – Input
Input RTD : Pt100
Input T/C : K, J and T
Input: mV
Minimum Span See table below
Technical Features – Output/Power Supply
Output : 4..20 mA
Supply : 14..40 VDC, Polarity Protected
Supply Effect : 0.002%/V
Input RTD : Pt100
Input T/C : K, J and T
Input: mV
Minimum Span See table below
Technical Features – Output/Power Supply
Output : 4..20 mA
Supply : 14..40 VDC, Polarity Protected
Supply Effect : 0.002%/V
Other Features
Zero Drift : ± 0.025%/°C
Span Drift : ± 0.01%/°C
Burnout : Upscale
Load Capability : Vbat-14V / 20 mA
Ambient Operating Temp. : -20...+ 80°C.
Housing Dimension : 22.5 x 79 x 85.5 mm
Zero Drift : ± 0.025%/°C
Span Drift : ± 0.01%/°C
Burnout : Upscale
Load Capability : Vbat-14V / 20 mA
Ambient Operating Temp. : -20...+ 80°C.
Housing Dimension : 22.5 x 79 x 85.5 mm
Input and Range Table
Input |
Range °C |
Min Span °C |
|
Thermocouple | K |
0... 1200 | 150 |
J |
0... 900 | 150 | |
T |
0... 400 | 150 | |
RTD | Pt100 | -50... 400 | 50 |
mV | mV | 100... 160mV |